j9com九游会

    Xiamen Teshow Co.,Ltd
    +86-592-2225929 
    ritazhousy@sina.com

    MA04D

      详细说明

      Features

      1.Standard DIN rail mount, plug-in terminals, easy to install, serial connection for different device.

      2.Controller with dual LED display, various indicators, four setting buttons, the configuration can be carried out even without master device

      3.Modbus RTU communication protocol, support 03H read, read multiple points, 06H write single point, 10H write multiple points, 03H read maximum 36 bytes one time, and 10H write 20 bytes one time

      4.Thermocouple inputs, 0.3% accuracy

      5.24VDC Power suplly for maximum safety

      6. ℃/℉ display selectable

      7.Maximum 15 units can be saisy chined together

      8.Heating or cooling selectable

      9.Four outputs,PID control mode or ON/OFF control mode selectable,direct/reverse control configurable for each loop

      10.Auto/Manual control bumpless transfer

      11.Soft-start for analog output

      12.Run/stop function

       

       

       

      Ordering information

      CODE:

       

      1.     Factory default input

      Input   Code

      Input type and range

      K

      K                             -30    to  1300℃/-20  to  2372      ℉

      E

      E                              -30  to  600℃/-20    to  1112    ℉

      J

      J                              -30  to  800℃/-20    to   1472    ℉

      N

      N                             -30  to  1300℃/-20  to  2372    ℉

      W

      Wu3_Re25                    600  to  2000℃/1000  to  3632  ℉

      S

      S                              0    to  1600℃/0    to    2912   ℉

      T

      T                             -30   to   400℃/-20  to    752    ℉

      R

      R                              0    to   1700℃/0  to    3092    ℉

      B

      B                             200   to   1800℃/400  to  3272  ℉

      Remark”The accuracy for S and R is not accurate if the temperature lower than 200℃

       

      2.     Main output OP1/OP2/OP3/OP4

      OP1 and OP2 output must be same,OP3 and OP4 must be the same

      Code

      OP1/OP2

      OP3/OP4

      1

      Relay 3A/250V

      Relay 3A/250V

      2

      Voltage pulse 12VDC

      Voltage pulse 12VDC

      3

      Voltage pulse 12VDC

      Relay 3A/250V

      4

      Relay 3A/250V

      Voltage pulse 12VDC

      9

      Analog output DA

      Analog output DA

       

       

      3.     Main output OP1/OP2/OP3/OP4 are analog output

       

      N

      Not analog output

      2

      DC 0~20mA

      8

      DC 4~20mA

      5

      DC 0~5V

      6

      DC 0~10V

      7

      DC 1~5V

       

      For example:MA04D-652-K-1-N

      Remark: MA04, 4 loops controller, OP1 and OP2 relay output, OP3 and OP3 output

      next item: MA04C
      Hot products

      Write To Us

      Please fill out the form and your request will be answered within one working day.

      j9com九游会