MA04C

    详细说明

    Features

    1.Standard DIN rail mount, plug-in terminals, easy to install, serial connection for different device.

    2.Controller with dual LED display, various indicators, four setting buttons, the configuration can be carried out even without master device

    3.Modbus RTU communication protocol, support 03H read, read multiple points, 06H write single point, 10H write multiple points, 03H read maximum 36 bytes one time, and 10H write 20 bytes one time

    4.Thermocouple inputs, 0.3% accuracy

    5.24VDC Power suplly for maximum safety

    6. ℃/℉ display selectable

    7.Maximum 15 units can be saisy chined together

    8.Heating or cooling selectable,heating+cooling control configurable

    9.Four outputs,2 main outputs and 2 auxiliary outputs

    Two Auxiliary outputs AU1 and AU2 can be configured for different functions

    (1) AU1 and AU2 can be assigned as the high/low output for OP1 and OP2 

    (2) AU1 and AU2 can be assigned as the cooling output of OP1 and OP2  

    (3) AU1 and AU2 can be assigned as the I/O port of the digital outputs

    10.PID control mode or ON/OFF control mode selectable

    11.Soft-start for analog output

    12.Run/stop function

    13.Auto/Manual control bumpless transfer

      

    Ordering information

    CODE:

     

    1.     Factory default input

    Input   Code

    Input type and range

    K

    K                             -30    to  1300℃/-20  to  2372      ℉

    E

    E                              -30  to  600℃/-20    to  1112    ℉

    J

    J                              -30  to  800℃/-20    to   1472    ℉

    N

    N                             -30  to  1300℃/-20  to  2372    ℉

    W

    Wu3_Re25                    600  to  2000℃/1000  to  3632  ℉

    S

    S                              0    to  1600℃/0    to    2912   ℉

    T

    T                             -30   to   400℃/-20  to    752    ℉

    R

    R                              0    to   1700℃/0  to    3092    ℉

    B

    B                             200   to   1800℃/400  to  3272  ℉

    Remark”The accuracy for S and R is not accurate if the temperature lower than 200℃

     

     

    2.     OP1 and OP2 output must be same,AU1 and AU2 output must be the same

     

    Code

    Main output OP1/OP2

    Auxiliary output AU1/AU2

    1

    Relay 3A/250V

    Relay 3A/250V

    2

    Voltage pulse 12VDC(SSR)

    Voltage pulse 12VDC(SSR)

    3

    Voltage pulse 12VDC(SSR)

    Relay 3A/250V

    4

    Relay 3A/250V

    Voltage pulse 12VDC(SSR)

    5

    Analog mV /mA

    Relay 3A/250V

    6

    Analog mV /mA

    Voltage pulse 12VDC(SSR)

    7

    Relay 3A/250V

    Analog mV /mA

    8

    Voltage pulse 12VDC(SSR)

    Analog mV /mA

    9

    Analog output DA

    Analog output DA

    Remark :The OP1 and OP2 must be the same,AU1 and AU2 output must be the same,AU1 and AU2 can be configured as alarm output for OP1 and OP2 or cooling output for OP1 and OP2 and also can be assigned as the I/O port for digital outputs

     

    3.     Main output OP1/OP2

     

    N

    Not analog output

    2

    DC0~20Ma

    8

    DC 4~20mA

    5

    DC 0~5V

    6

    DC 0~10V

    7

    DC 1~5V

     

     

    4.     Assign a factory default output function to AU1(the physical output type is the same as AU2)

     

    A1

    AU1 assigned as deviation high alarm for #1 channel(Relay)

    WV

    AU1 assigned as cooling output for #1 channel(Voltage pulse)

    B1

    AU1 assigned as deviation low alarm for #1 channel(Relay)

    W2

    AU1 assigned as cooling output for #1 channel(0~20mA)

    H1

    AU1 assigned as the process value high alarm for #1   channel(Relay)   

    W8

    AU1 assigned as cooling output for #1 channel(4~20mA)

    J1

    AU1 assigned as the process value low alarm for #1 channel(Relay)

    W5

    AU1 assigned as cooling output for #1 channel(0~5VDC)

    0

    AU1 used as I/O port(Relay)

    W6

    AU1 assigned as cooling output for #1 channel(0~10VDC)

    WM

    :AU1 used as cooling output for #1 channel(Relay)

    W7

    AU1 assigned as cooling output for #1 channel(1~5VDC)

     

     

    5. Assign a factory default output function to AU2(the physical output type is the same as AU1)

     

    A2

    AU2 assigned as deviation high alarm for #2 channel(Relay)  

    B2

    AU2 assigned as deviation low alarm for #2 channel(Relay)

    H2

    AU2 assigned as the process value high alarm for #2 channel(Relay)

    J2

    AU2 assigned as the process value low alarm for #2 channel(Relay) 

    A1

    AU2 assigned as deviation high alarm for #1 channel(Relay) 

    WV

    AU1 assigned as cooling output for #2 channel(Voltage pulse)

    B1

    AU2 assigned as deviation low alarm for #1 channel(Relay)  

    W2

    AU1 assigned as cooling output for #2 channel(0~20mA)

    H1

    :AU2 assigned as the process value high alarm for #1   channel(Relay)

    W8

    AU1 assigned as cooling output for #2 channel(4~20mA)

    J1

    :AU2 assigned as the process value low alarm for #1   channel(Relay) 

    W5

    AU1 assigned as cooling output for #2 channel(0~5VDC)

    O

    AU2 used as I/O port(Relay)

    W6

    AU1 assigned as cooling output for #2 channel(0~10VDC)

    WM

    AU2 used as cooling output for #2 channel(Relay)

    W7

    AU1 assigned as cooling output for #2 channel(1~5VDC)

     

     

    Example:MA04C-653-K-5-8-A1-A2, Dual loop Din rail mount controller, type K input for both channel, 4-20mA for OP1 and OP2, Relay for AU1 and AU2, AU1 and AU2 can be assigned as cooling output or alarm output for #1 and #2 channel

     

     